Container WWTP

Quick contact
Quick contact
to your WWTPs and
WTPs specialist
+420 381 203 211
+420 737 240 800
Branches and offices

Waste water treatment
Container WWTP


For:Manufacturing companies, hotels, camps, small towns and villages

Description

BioCleaner BC 20 - BC 150


Gallery


Application

  • For treating of communal waste water (from bathrooms, sanitary facilities, washing machines, kitchen, etc.) and biologically dissolvable industrial waste water.
    • Low operating expenses are ensured by various programmable regimes of operating (seasonal operating, etc.)
    • WWTP technology can be installed to current septic tanks or basins
    • WWTP BioCleaner® is certificated according to standard CSN EN 12566-3-A1

Savings

  • Low operating expenses are ensured by various programmable regimes of operating
  • The programmes are designed for immediate or expected loading (in compliance with attendance, occupation or the season)

Maintenance

  • Maintenance requirements are lowered by an automatic exhaustion of filth and foam on the water surface – no necessity to do it manually
  • The technology for treatment ensures low production of sludge and so it decreases the necessity to de-sludge frequently

Design advantages

  • Excellent quality
    • We don’t use recycled plastic material
    • We use only the highest quality certificated plastic material from Röchling and IMG – guaranteed mechanical standard requirements for the tank
    • Mechanical characteristics of the tank are checked by a static calculation
  • Regular operating of the WWTP and internal pumping is ensured by hydro-pneumatic pumps
    • There is no other pump for the operation of the WWTP
    • Fault sources removed
  • The treatment plant BioCleaner ensures functionality even during power supply breakdowns
  • The treatment plant doesn’t require any special insulating for operation in winter
  • Current septic tanks may be remade for the WWTP by installation of a technological kit
  • Plastic self-supporting construction doesn’t require expensive building preparations
  • The WWTP can be fitted under, halfway or above the surface of the terrain (after adjustement)

Technology

  • The treating effect of the BioCleaner® technology achieves up to 98 %
  • Treated water may be used as water for watering of gardens or as fire fighting water
  • Part of the technology can be a tank for excess sludge (on request)

Technical Specification

Parameters of the treated water

Indicator Required values at the outflow* BioCleaner® **
  “p” [mg/l] “m” [mg/l] [mg/l]
BOD5 40 80 15 - 25
COD 150 220 55 - 90
SS 50 80 15 - 25

*) Required values for indicators of pollution at the outflow according to NV 23/2011 Sb. for WWTP to 500 EO
**) Usual average values at the outflow in the WWTP BioCleaner®

Basic parameters for WWTP BioCleaner®

BioCleaner®   BC 16 BC 20 BC 25 BC 30 BC 40 BC 50 BC 100 BC 150
Number of people connected to the WWTP   15~20 20~25 25~30 30~35 40~45 45~85 90~125 125~170
Amount of waste water Q24 [m³/day] 2.4 3.0 3.8 4.5 6.0 7.5 15.0 22.5
Electric input when loaded [W] 280 550 1 100 1 100 1 100 1 500 1 500 1 500
Max. energy. demands [kWh/day] 6.7 13.2 26.4 26.4 26.4 36.0 36.0 36.0
Weight rectangular tank ( cylindric tank ) [kg] 600
(310)
800
(370)
1 200
(490)
1 800
(540)
1 800 2 400 2 500 3 000
Dimensions rectangular tank L [m]
W [m]
H [m]
2.2
2.0
2.6
3.0
2.2
2.1
3.5
2.2
2.1
4.0
2.2
2.6
4.0
2.2
2.6
4.0
2.2
3.1
5.2
2.4
3.1
6.2
2.4
3.1
Dimensions cylindric tank Ø×H [m] 2.1×2.5 2.4×2.4 2.4×2.8 2.4×3.2 - - - -

rectangular tank Rectangular tank
cylindrictank Cylindric tank

Components and accessories

WWTP Covers

  • Timber cover (walkable)
  • Laminated cover (walkable)
  • Log cabin

Other

  • Attachments for the WWTP
  • Chemical condensation of phosphorus / oxygen probe
  • Control unit COMFORT with blower (assembly kit)

WWTP capacity calculator

Approximate calculation of required capacity WWTP

Calculate the required capacity of the wastewater treatment plant, the average amount of waste water per day (Q24) and the daily contribution of substance pollution (BOD5) for the family home, accommodation or production hall. Calculation form allows you to choose the optimal treatment plant.

count Q24 (m³/day) BOD5 (kg/day)
Family House person
Hostel, pension bed
Restaurant chair
Restaurant kitchen without warm chair
Camp, summer camp bed
School student
School with dining student
Factories, trading companies, etc. - clean work employee
Factories, trading companies, etc. - dirty work employee
Total:
Hydraulic load / biological load / total inflow to the wastewater corresponding population equivalent (PE):
Type of WWTP:

It is based on the calculation of water needs and Act No. 274/2001 Coll., Decree No. 428/2001 Coll., Annex 12 to the specific need of water for 1 PE - 150 L/day, equivalent to 1 PE pollution - BOD5 60g/pers./day.